I finally hit 1,000 panels swapped and the number that shocked me was 63 bad zone resistors
Hit 1,000 panel replacements across my route here in Toledo last Friday. Out of all those jobs I counted 63 where the old install had a zone resistor stuffed in the can instead of at the device, and most of those were causing random faults nobody could chase down. The resistor in the panel trick works fine until moisture or vibration gets to it, then you get a zone that opens and closes at 3am. Now I check for panel-side resistors first on every trouble call and it saves me a ton of meter time. Anyone else keep a running count of repeat offender wiring habits you find on takeovers?
Panel side resistors are a lazy habit, plain and simple. Guy who used to work my area loved doing that, and I found FOUR in one building where the resistor was just twisted on with wire nuts hanging loose in the can. Every one of those zones was flaky in wet weather. I keep a list in my phone now: panel resistors, spliced commons, devices mounted on furring strips. Takes two minutes to check and saves hours of guessing later.